• home
  • login
  • korean

ȸ»ç¼Ò°³

M74 SERIES

M74 SERIES

4 CH modular type PID controller

High reliability with the complete insulation and efficient space arrangement with the compact structure. Simple maintenance and repair with the structure of separating base from the main body. Unnecessary communication between modules and power wiring through extension connectors. Easy and convenient parameter setting (on-site) by using device integrated management program.

  • Ultra compact size (65%Compared to other brand)
  • Easy and convenient parameter setting with the console
  • RS485 communication with fully independent isolation structure (PC/TL-Link, Modbus-ASCII/RTU)
  • Simple maintenance and repair by separate structure of main body and base
  • Support electronic address and communication setting
  • Compete insulation structure between each input and input/output (Withstanding voltage 1,000V AC or higher)
  • Providing device integrated management program to ease remote monitoring and setting
  • Support free output port setting to simultaneously control transmission output and heating/cooling
  • Unnecessary communication between modules and power wiring through extension connectors

General Specification

Channel Control input, output 4 channels
Power supply 24V DC
Allowable voltage range 90~110% of rated voltage
Power Consumption Max. 5W (for max. load)
Display method No display - Parameter setting and monitoring control in external devices (exclusive console, touch panel, PC, PLC, etc.)
Input type
Thermocouple (T.C) Thermoresistance (RTD) Analog (Variable within the input range)
K(CA), J(IC), E(CR), T(CC) KPT 100(KS) Voltage Current
R(PR), B(PR), S(PR), L(IC) JPT 100(JIS) 0~5V, 1~5V, 0~10V 0~20mA
4~20mA
N(NN), U(CC), C(W5), D(W3) PT 100(DIN) 0~100mV, -10~20mV
Sampling cycle Minimum 50 ms (4 channels simultaneous variable sampling control)
Measurement Accuracy 0.3% FS+1 digit
Control method Simultaneous heating and cooling, heating, cooling control: On/Off control, P, PI, PID control(Super 2 degrees of freedom)
Output Transmit RET (4~20 mA DC), load resistance 500 or less (Actual resolution 1/6000)
Control SSR(Voltage pulse) DC 12V 25mA(Built-in short circuit protection) Voltage pulse (Time proportional PID output or On/Off output)
SCR(current) DC 4~20mA (Load resistance 500 ohm or less)
Com-munication Upper device Modbus-ASCII, RTU, PC or TL-Link
PC loader Console(Dedicated display controller), USB Interface Cable(Option)
Proportional width(P)) Thermocouple, Thermoresistance: 0.1~999.9 ¡ÆC, Analog Voltage, Current Input: 0.1~999.9 Digit
Integral Time (I) 0 ~ 3600 Sec.
Derivative Time (D) 0 ~ 3600 Sec.
Control Cycle (CT) Control Cycle (CT)
Blackout Compensation Approx. 10 years (Non-Volatile Semiconductor Memory Method)
Insulation Resistance 100 M more (500V DC megger)
Insulation Type Double insulation or reinforced insulation
(Symbol: withstand voltage between measurement input and power terminal : 1KV or higher)
Withstand voltage 1,000V AC 50/60Hz for 1 minute (between each input terminal, between input and output terminals, between input and power terminals)
Vibration resistance 5~55Hz(Period of 1 minute) width 0.75mm in each X, Y, Z direction for 2 hours
Noise Immunity Square wave noise by noise simulator (pulse width 1us) +/-1KV
Environ- Operating temperature Operating temperature -10 to 50¡ÆC, preservation: -20 to 60¡ÆC
Operating humidity 35-85 % RH, preservation: 35-85% RH
Weight Approx. 230g (Unit: Approx. 110g)

M74 Wiring

M74

Dimension

M74